Group code f-e-e6d15i59c-: “chiller <C> pump inverter Uv3”

Situation

Solution

The DC bus voltage is below the limits due to insufficient power supply voltage

Check power network voltage (star/delta).

Incorrect wiring of the input power of the inverter

Check connections between mains and pump inverter. Ensure the inverter power terminals are tightened properly.

Malfunction Pump inverter.

Replace Pump inverter. See service manual chiller.